How often should a fire alarm be serviced?

Last checked November 2026

For a fire alarm in a business, a block of flats or other non-domestic building, the short answer is: a professional service at least every six months, and a quick test by you every week.

What BS 5839-1 recommends

BS 5839-1 is the British Standard for fire alarm systems in non-domestic buildings. It recommends that the system is inspected and serviced by a competent person at intervals of no more than six months.

That’s the usual starting point. Your fire risk assessment or insurer might ask for more, for example in a large or busy building, or one where a fault could go unnoticed. Under the Regulatory Reform (Fire Safety) Order 2005, the “responsible person” for the building, usually the employer, owner or managing agent, has to make sure fire safety equipment is kept in good working order. Regular servicing is how you show that.

The weekly test you do yourself

As well as the service visits, someone on site should test the alarm every week. It only takes a minute:

  • Set off the alarm from a manual call point (the red “break glass” boxes), using the test key.
  • Use a different call point each week, working your way round the building.
  • Check the sounders can be heard, then reset the panel.
  • Write the date, time and which call point you used in the fire alarm log book.

Doing it at the same time each week helps, because people get used to it and know it’s a test. If the alarm sends a signal to a monitoring centre, let them know before you test.

What happens on a service visit

A service is more than pressing a button. The engineer will normally:

  • Look through the log book and the panel’s event history for faults or false alarms since the last visit.
  • Check the control panel, its batteries and charger, and any fault or warning lights.
  • Test smoke and heat detectors, call points, sounders and any flashing beacons, working through the system over the year.
  • Check any links to other systems, such as door holders that release fire doors or smoke vents that open when the alarm goes off.
  • Check whether anything in the building has changed, such as new walls, a change of use or blocked detectors, that could stop the system working properly.
  • Record what was done and anything that needs fixing, and give you a certificate.

Signs your fire alarm needs attention sooner

Don’t wait for the next service if you notice any of these:

  • A fault or warning light on the panel that won’t clear.
  • False alarms, especially from the same detector more than once.
  • A sounder that’s quiet or silent during the weekly test.
  • Building work, a new partition or a change in how a room is used.

False alarms are more than a nuisance. They disrupt the building, and if people get used to them they may not react when there’s a real fire. Most have a cause that can be found and fixed, such as a detector in the wrong place or one that needs replacing.

What about smoke alarms at home?

Ordinary homes usually have smoke alarms rather than a full fire alarm system. Fire and rescue services recommend testing them at least once a month by pressing the test button. If they’re mains-powered and linked together, pressing one should set them all off. Smoke alarms don’t last forever: most manufacturers say to replace them after about ten years.

Landlords have their own rules. Our guide do landlords need a fire alarm? explains them.

Keep the paperwork

If there’s ever a fire, an insurance claim or a visit from the fire service, you’ll be asked to show the system has been looked after. That means a log book with the weekly tests and certificates for each service. With us, we complete your certificate or service report on site and email it to you before the job is closed. It has a QR code to check it’s genuine and is kept in your online portal.

We service fire alarm systems across Hertfordshire, London and nearby, including systems someone else fitted, and can look after your emergency lighting and extinguishers on the same visit. See our servicing and maintenance page.

Questions people ask

How often should a fire alarm be serviced?

For a fire alarm system in a business, block of flats or other non-domestic building, BS 5839-1 recommends a service by a competent person at intervals of no more than six months. Your fire risk assessment or insurer may ask for more.

How often should I test my fire alarm myself?

Once a week, from a different manual call point each time, and write it in the log book. It only takes a minute.

What happens if my fire alarm isn’t serviced?

Faults can go unnoticed, so the alarm may not work properly when it’s needed. It can also cause problems with your insurer or the fire service, because you can’t show the system has been looked after.

Can you service a fire alarm someone else fitted?

Yes. We service and repair fire alarm systems whoever installed them, as long as we can get the parts and access codes we need. We’ll tell you after the first visit if anything needs attention.

This is general guidance, not legal advice. Rules change, and what applies to you depends on your building and how it’s used. Your fire risk assessment, insurer or local council can tell you exactly what you need.