Emergency lights come on by themselves when the power fails, so people can find their way out. Because they sit doing nothing most of the time, the only way to know they’ll work is to test them.

What BS 5266-1 asks for

BS 5266-1 is the British Standard for emergency lighting. It sets out two main tests:

  • Every month: a short function test.
  • Once a year: a full-duration test.

The monthly test

This is a quick check that every emergency light and exit sign switches on when the mains supply is cut.

  • Switch the emergency lights onto battery, usually with a key switch next to the light switch or near the distribution board.
  • Walk round and check every fitting and exit sign has come on.
  • Switch the mains back on, and check the charging lights on the fittings come back on.
  • Write the date, the result and any faults in the log book.

The test only needs to be long enough to see that each light works. Keep it short so the batteries aren’t drained.

The annual full-duration test

Once a year, the lights are run on battery for their full rated time, which is usually three hours, to prove the batteries can still last. Every fitting must stay lit for the whole time.

Afterwards the batteries need time to recharge, which can take up to a day. During that time the building has less protection, so the test is best done when the building is quiet, or done in stages so neighbouring lights aren’t all flat at once.

Self-testing lights

Some emergency lights test themselves automatically and show a coloured light or send a report if something fails. They save time, but someone still needs to check the results regularly and write them down.

When a light fails

The usual cause is the battery, which wears out over time. Sometimes it’s the lamp, the charging circuit or the fitting itself. Failed lights should be fixed as soon as possible and retested, with the repair noted in the log book.

Who is responsible?

In a business or the shared parts of a block of flats, it’s the person responsible for fire safety in the building, often the owner, employer, landlord or managing agent. They can carry out the monthly test themselves and have a competent person do the annual test and repairs.

Questions people ask

How often should emergency lighting be tested?

A short functional test every month and a full-duration test once a year, usually three hours, with the results written down. That’s what BS 5266-1 recommends.

Can I do the monthly emergency lighting test myself?

Yes, if someone shows you how. It means briefly cutting the mains supply to the lights, usually with a test key switch, and checking each light comes on. The annual test is best done by an engineer.

This is general guidance, not legal advice. Rules change, and what applies to you depends on your building and how it’s used. Your fire risk assessment, insurer or local council can tell you exactly what you need.

Want us to take a look? Our local engineers install and look after emergency lighting across Hertfordshire, London and nearby. Call us or ask for a free quote.

More on our emergency lighting service and fire safety for landlords.